一、圖紙基礎(chǔ)信息識別

1、 Identification of basic information on drawings

比例與圖例

Proportion and legend

濟南地區(qū)常用 1:100 或 1:200 比例,注意風(fēng)管尺寸標注單位(mm 或 m)

The commonly used scale in Jinan area is 1:100 or 1:200, pay attention to the unit of air duct size annotation (mm or m)

重點識別本地常用符號:

Key identification of commonly used local symbols:

? 排煙風(fēng)管(紅色虛線)

Smoke exhaust duct (red dashed line)

? 新風(fēng)管(藍色實線)

Fresh air duct (solid blue line)

? 消聲器(濟南地鐵項目常用阻抗復(fù)合式符號)

Silencer (commonly used impedance composite symbol for Jinan Metro project)

標高系統(tǒng)

Elevation system

濟南地區(qū)地下室層高普遍≥3.5m,注意風(fēng)管底標高標注(如 F+2.8m 表示距地 2.8 米)

The basement floor height in Jinan area is generally ≥ 3.5m. Pay attention to the elevation marking of the air duct bottom (such as F+2.8m indicating a distance of 2.8 meters from the ground)

結(jié)合《山東省建筑防煙排煙系統(tǒng)技術(shù)標準》,排煙風(fēng)管距可燃物間距≥150mm

According to the Technical Standards for Building Smoke Control and Exhaust Systems in Shandong Province, the distance between the exhaust duct and combustible materials should be ≥ 150mm

二、系統(tǒng)布局分析技巧

2、 System layout analysis skills

氣流組織路徑

Airflow organization path

濟南夏季主導(dǎo)風(fēng)向東南風(fēng),進風(fēng)口應(yīng)避開污染源(如工業(yè)區(qū)、交通干道)

The dominant wind direction in Jinan during summer is southeast, and the air inlet should avoid pollution sources such as industrial areas and traffic arteries

某商業(yè)綜合體項目案例:新風(fēng)管避開地下車庫排風(fēng)井,采用屋頂高位進風(fēng)(高度≥5m)

Case study of a commercial complex project: The new air duct avoids the exhaust shaft of the underground garage and adopts high-level air intake on the roof (height ≥ 5m)

管道坡度設(shè)計

Pipeline slope design

冷凝水排水管坡度≥3‰(GB 50738-2011),濟南濕度大需特別注意

The slope of the condensate drainage pipe is ≥ 3 ‰ (GB 50738-2011), and special attention should be paid to the high humidity in Jinan

人防地下室風(fēng)管坡度需結(jié)合排水地漏位置,坡度方向箭頭指向排水點

The slope of the air duct in the civil air defense basement should be combined with the position of the drainage floor drain, and the slope direction arrow should point to the drainage point

三、關(guān)鍵節(jié)點識圖要點

3、 Key Points for Key Node Mapping

風(fēng)管與設(shè)備連接

Air duct and equipment connection

風(fēng)機進出口需設(shè)置軟連接(長度 150-300mm),濟南某醫(yī)院項目采用硅鈦合金軟接

Soft connections (length 150-300mm) are required for the inlet and outlet of the fan. A hospital project in Jinan uses silicon titanium alloy soft connections

防火閥安裝位置:距墻表面≤200mm(GB 50016-2014),需與圖紙標注一致

Installation position of fire damper: ≤ 200mm from the wall surface (GB 50016-2014), consistent with the drawing markings

20221114013805825.jpg

變徑與彎頭處理

Variable diameter and elbow treatment

矩形風(fēng)管長邊>630mm 時需設(shè)置導(dǎo)流葉片,某地鐵車站彎頭采用 S 型導(dǎo)流板

When the length of the rectangular air duct is greater than 630mm, guide vanes need to be installed, and an S-shaped guide plate is used for the elbow of a subway station

濟南西站風(fēng)管變徑段長度按 1:4-1:6 比例設(shè)計,減少局部阻力損失

The length of the variable diameter section of the air duct at Jinan West Station is designed in a ratio of 1:4-1:6 to reduce local resistance losses

四、材料與保溫要求

4、 Material and insulation requirements

風(fēng)管材質(zhì)識別

Identification of duct material

地下車庫排煙風(fēng)管需采用厚度≥1.2mm 鍍鋅鋼板(濟南消防驗收強制要求)

The smoke exhaust duct of the underground garage must be made of galvanized steel plate with a thickness of ≥ 1.2mm (mandatory requirement for Jinan fire inspection)

人防工程優(yōu)先選用 3mm 厚鋼板風(fēng)管,配合 L50*5 角鋼法蘭

Priority should be given to using 3mm thick steel plate air ducts for civil air defense projects, in conjunction with L50 * 5 angle steel flanges

保溫層標注

Insulation layer labeling

空調(diào)風(fēng)管保溫層厚度≥30mm(橡塑材料,導(dǎo)熱系數(shù)≤0.034W/(m?K))

The insulation layer thickness of the air conditioning duct is ≥ 30mm (made of rubber material, with a thermal conductivity coefficient of ≤ 0.034W/(m? K))

濟南地區(qū)需注意冷凝控制,保溫層外需設(shè)置防潮層(鋁箔貼面)

Attention should be paid to condensation control in Jinan area, and a moisture-proof layer (aluminum foil veneer) should be installed outside the insulation layer

五、與其他專業(yè)協(xié)同要點

5、 Key points for collaboration with other professions

管線綜合原則

Comprehensive principle of pipeline

風(fēng)管避讓原則:有壓管讓無壓管,小管線讓大管線

Principle of avoiding air ducts: pressure pipes should be replaced by non pressure pipes, and small pipes should be replaced by large pipelines

某綜合體項目實例:風(fēng)管與噴淋管交叉時,風(fēng)管上翻 300mm 避開噴淋頭

Example of a certain integrated project: When the air duct intersects with the sprinkler pipe, the air duct is flipped up 300mm to avoid the sprinkler head

預(yù)留孔洞標注

Reserved hole marking

穿墻套管尺寸需比風(fēng)管大 100mm,濟南地區(qū)預(yù)留孔洞需考慮保溫層厚度

The size of the through wall sleeve should be 100mm larger than the air duct, and the reserved holes in Jinan area need to consider the thickness of the insulation layer

人防套管需標注密閉肋位置(距墻表面 50mm)

The position of the sealing rib should be marked on the civil air defense casing (50mm away from the wall surface)

本文由濟南通風(fēng)管道友情奉獻.更多有關(guān)的知識請點擊: http://www.fsjt-gov.com我們將會對您提出的疑問進行詳細的解答,歡迎您登錄網(wǎng)站留言.

This article is a friendly contribution from Jinan ventilation ducts For more information, please click: http://www.fsjt-gov.com We will provide detailed answers to your questions. You are welcome to log in to our website and leave a message

上一篇:為什么使用山東通風(fēng)管道
下一篇:濟南通風(fēng)管道類型、特性、嚴謹

推薦產(chǎn)品

  • 廚房排煙
  • 廚房排煙
  • 軸流風(fēng)機
  • 不銹鋼制品

本站圖片均由網(wǎng)站所有方提供,部分圖片來源于網(wǎng)絡(luò),如有任何疑問請及時與我們聯(lián)系,未經(jīng)溝通本站不承擔相關(guān)法律責任!